Mitsubishi P2 error code

Liquid pipe temperature sensor fault

The sensor on the indoor unit's liquid refrigerant pipe is reading as short-circuited or disconnected.

What to check

Checked against 4 official sourcesReviewed October 2026

Worth repairing?

Worth fixing

Most of the causes Mitsubishi lists are sensor or wiring repairs. The engineer should also rule out a refrigerant circuit problem, which is on the same list.

Got a quote? Check if it's worth paying

Can you do it yourself?

Engineer only

Engineer visit

Before you start

  • Unplug it before you touch anything inside.

What it means

Mitsubishi's thermistor TH2. It counts as faulty at 90°C or more (short) or -40°C or less (open), and the unit pauses for 3 minutes first. Mitsubishi notes a refrigerant circuit fault can also push this reading to extremes. With a wireless remote, the self-check reports it as 2 beeps and 2 flashes, the same as P9.

What to check, in order

  1. Write down the code

    Note the code and unit number, as Mitsubishi's operation manual asks.

  2. Switch off and on once

    Turn the system off at the breaker or isolator and back on. If P2 returns, leave it off and book a repair.

When to call an engineer

Call an air conditioning engineer (UK) or HVAC technician (US). Mitsubishi lists a faulty sensor, a poor contact at its connector, a broken sensor wire, a refrigerant circuit fault that makes the pipe extremely hot or cold, or a faulty indoor control board.

A repair visit will usually check the sensor's reading and its wiring.

Before you book
  • Note the model and serial number. They're on a label on the side of the indoor unit, and on the outdoor unit.
  • Write down the exact code, and what the appliance was doing when it appeared.
  • Check whether it's still under warranty. If it is, the repair may cost you nothing.

Quick answers

What does the Mitsubishi P2 error code mean?

The sensor on the indoor unit's liquid refrigerant pipe is reading as short-circuited or disconnected. Mitsubishi's thermistor TH2. It counts as faulty at 90°C or more (short) or -40°C or less (open), and the unit pauses for 3 minutes first. Mitsubishi notes a refrigerant circuit fault can also push this reading to extremes. With a wireless remote, the self-check reports it as 2 beeps and 2 flashes, the same as P9.

Can I fix Mitsubishi P2 myself?

Engineer only (engineer visit). Start with: write down the code; switch off and on once. Call an air conditioning engineer (UK) or HVAC technician (US). Mitsubishi lists a faulty sensor, a poor contact at its connector, a broken sensor wire, a refrigerant circuit fault that makes the pipe extremely hot or cold, or a faulty indoor control board.

Is Mitsubishi P2 worth repairing?

Worth fixing. Most of the causes Mitsubishi lists are sensor or wiring repairs. The engineer should also rule out a refrigerant circuit problem, which is on the same list.

Checked against

Last reviewed October 2026. Manufacturers update their pages, and your manual is the final word. Spotted a mistake? Email contact@appliance-error-codes.com.

Another code on the display?

Look it up in seconds

344 codes from 24 brands, each one checked against the maker's own manuals and support pages.

↑ ↓ to moveEnter to openTip: add the brand, like samsung 4e